Research on anti-overstep of downhole power supply system based on signal injection and decentralized detection

WANG Yongjun(), LIU Xin   

  1. Equipment Maintenance Center, Shendong Coal Group, National Energy Group, Yulin Shaanxi 719300, China
  • Received:2023-03-11 Revised:2023-05-12 Published:2023-06-30

摘要:

为有效解决煤矿井下供电系统短路引起的越级跳闸问题,从注入信号分散检测单相接地故障原理出发,提出基于信号注入和分散检测相结合的单相接地故障选线理论,增加一个零序电流到故障电路中,将理想零序电流提供给故障系统,并利用模拟元件搭建测试系统测试注入信号检测部分,构建测试模型实现电网系统单相接地故障,并利用井下配电网数字光纤通信式保护器,解决井下供电系统发生故障后的快速、准确动作和故障隔离问题。结果表明:通过注入主频80 Hz,幅值40 mA的信号,信号滤波算法能够滤除工频及其谐波等信号的干扰,在注入信号的频率小范围偏移时,装置能准确检测和提取注入信号以便判断故障。

关键词: 信号注入, 分散检测, 供电系统防越级, 通信保护器, 电压互感器

Abstract:

In order to effectively solve the problem of overstep tripping caused by short circuit of the power supply system in coal mines, according to the principle of decentralized detection of single-phase grounding fault of injected signal, the single-phase grounding fault line selection theory was proposed based on the combination of signal injection and decentralized detection, and zero sequence current was added to the fault circuit to provide the ideal zero sequence current to the fault system. In addition, analog components were used to build a test system to test the injected signal detection part, and a test model was built to realize the single-phase grounding fault of the power grid system. Digital optical fiber communication protector of the underground distribution network was used to ensure rapid and accurate actions and fault isolation after the failure of the underground power supply system. The results show that by injecting a signal with a main frequency of 80 Hz and an amplitude of 40 mA, the signal filtering algorithm can filter out the interference of power frequency and harmonic signal. When the frequency of the injected signal is offset in a small range, the device can accurately detect and extract the injected signal to judge the fault.

Key words: signal injection, decentralized detection, overstep of power supply system, communication protector, voltage transformer