中国安全科学学报 ›› 2026, Vol. 36 ›› Issue (9): 85-93.doi: 10.16265/j.cnki.issn1003-3033.2026.09.0240

• 安全技术与工程 • 上一篇    下一篇

基于局部应用灭火系统的喷射气体冲力模型

马建琴1,2,3(), 杨帆1,2,3, 王皓轩1,2,3, 赵青松1,2,3   

  1. 1 应急管理部天津消防研究所, 天津 300381
    2 工业与公共建筑火灾防控技术应急管理部重点实验室, 天津 300381
    3 天津市消防安全技术重点实验室, 天津 300381
  • 收稿日期:2026-05-06 修回日期:2026-07-13 出版日期:2026-10-20
  • 作者简介:

    马建琴 (1983—),女,甘肃张掖人,硕士,副研究员,主要从事固定灭火系统技术开发、新型洁净灭火剂灭火技术和新能源锂离子电池火灾防控技术方面的研究。E-mail:。

    王皓轩 助理研究员;

    赵青松 助理研究员

  • 基金资助:
    国家重点研发计划项目(2023YFC3010203)

Gas discharge impulse model in local application fire systems

Ma Jianqin1,2,3(), Yang Fan1,2,3, Wang Haoxuan1,2,3, Zhao Qingsong1,2,3   

  1. 1 Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China
    2 Key Laboratory of Fire Protection Technology for Industy and Public Building, Ministry of Emergency Management, Tianjin 300381, China
    3 Tianjin Key Laboratory of Fire Safety Technology, Tianjin 300381, China
  • Received:2026-05-06 Revised:2026-07-13 Published:2026-10-20

摘要:

为解决局部应用灭火系统在扑救B类平面火灾时,喷射气体冲力兼具高效压火与诱发飞溅双重作用的安全技术问题,构建气体冲力预测模型并开展试验研究。首先,基于阵列式动态压力测量的气体冲力测试装置,精准量化喷嘴下方气体冲力场的空间分布与瞬态演化特征;其次,基于试验数据,建立综合喷射压力与时间的冲力预测模型;然后,构建包含压火与灭火2阶段的综合效能模型,基于火羽流理论建立火焰升力计算模型,确立喷射气体冲力大于火焰升力的临界灭火判据;最后,提出中心飞溅的表面张力判据与边缘溢出的几何形态判据,量化安全喷射的冲力阈值。结果表明:所建模型与装置可精准预测灭火所需的临界冲力与诱发飞溅的安全阈值,灭火成功发生在冲力峰值释放期及衰减初期,与理论判据预测一致;飞溅预测结果与试验观测结果吻合,验证了双重判据的有效性。

关键词: 局部应用, 灭火系统, 喷射气体冲力, 平面火, 火焰升力, 临界飞溅

Abstract:

To address the safety technical issue in local application fire suppression systems for Class B pool fires, where the gas discharge impulse plays a dual role of both highly effective flame knockdown and inducing splashing, a systematic gas discharge impulse prediction model was developed and experimental studies were conducted. Firstly, an array-based dynamic pressure measurement device was designed and fabricated to accurately quantify the spatial distribution and transient evolution of the gas discharge impulse field beneath the nozzle. Based on experimental data, a predictive model was established, incorporating both discharge pressure and duration. Secondly, a comprehensive fire suppression effectiveness model was constructed, which comprised two sequential phases: flame knockdown and extinguishment. A flame lift force calculation model based on plume theory was established, and the critical extinguishment criterion was defined as the gas discharge impulse exceeding the flame lift force. Finally, a surface tension criterion for central splash and a geometric morphology criterion for edge overflow were proposed innovatively to quantify the upper impulse threshold for safe discharge. The results demonstrate that the developed models and device can accurately predict both the critical impulse required for successful extinguishment and the upper safety limit for splashing. The extinguishment was observed to occur during the peak impulse release and early decay stages, which is consistent with the theoretical criterion prediction. The predicted splash behavior also agrees well the experimental observations, thereby validating the effectiveness of the dual-criterion approach.

Key words: local application, fire systems, gas discharge impulse, pool fire, flame lift force, critical splashing

中图分类号: