China Safety Science Journal ›› 2023, Vol. 33 ›› Issue (2): 152-158.doi: 10.16265/j.cnki.issn1003-3033.2023.02.0048

• Safety engineering technology • Previous Articles     Next Articles

Effect of detachable noise reduction board on fire temperature field in converter substation

KANG Ning1(), QIN Yiren1, ZHANG Jiaqing2,3,4, GUO Yi1,2,3, LIN Jin1, LU Shouxiang1,**()   

  1. 1 State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei Anhui 230026, China
    2 Electric Power Research Institute, State Grid Anhui Electric Power Co., Ltd., Hefei Anhui 230601, China
    3 State Grid Laboratory of Fire Protection for Transmission and Distribution Facilities, Hefei Anhui 230022, China
    4 Anhui Province Key Laboratory of Electric Fire and Safety Protection, Hefei Anhui 230022, China
  • Received:2022-09-10 Revised:2022-12-15 Online:2023-02-28 Published:2023-08-28

Abstract:

In order to coordinate the relationship between the noise reduction board and fire emergency response in the converter station, and overcome the difficulties such as high cost and difficulty of the test, a fire dynamics software was used to simulate the fire scenes started at the transformer top and tap switch in the enclosed space of low voltage converter transformer, considering detachable, uncovered and undetachable noise reduction boards. Based on the temporal and spatial evolution data of fire temperature, the characteristic of fire temperature in converter transformer enclosure space using a detachable noise reduction board was discussed. The results show that the board melted and fell off 206 seconds after the transformer top fire, while the above behavior occurred 485 seconds after the tap switch fire. Under the action of the detachable noise reduction board, the temperature variation at the top of the transformer is rising, suddenly falling and rising again, because the enclosed space is opened and cooled. The detachable noise reduction board can reduce the heating rate at the oil pillow and the plugging structure of valve hall.

Key words: converter transformer fire, temperature field, detachable, noise reduction board, oil pillow, plugging structure