China Safety Science Journal ›› 2025, Vol. 35 ›› Issue (8): 93-99.doi: 10.16265/j.cnki.issn1003-3033.2025.08.1319

• Safety engineering technology • Previous Articles     Next Articles

Study on characteristics of Chinese liquor pool fire under action of liquid CO2

ZHANG Yutao(), BIAN Jing, GUO Qiang, BAI Kexin, LI Xing, ZHANG Yuanbo   

  1. College of Safety Science and Engineering, Xi'an University of Science and Technology, Xi'an Shaanxi 710054, China
  • Received:2025-03-24 Revised:2025-06-08 Online:2025-08-28 Published:2026-02-28

Abstract:

To explore more efficient fire extinguishing techniques for Chinese liquor warehouses, based on the similarity theory, an experimental bench for liquid CO2 fire extinguishing with dimensions of 5 000 mm×2 400 mm×2 900 mm was constructed. An in-depth study was conducted on the changes in Chinese liquor quality, temperature distribution, and gas volume fraction during the process of extinguishing Chinese liquor pool fire using liquid CO2 fire extinguishing systems with different combustion disk diameters. The research results indicate that liquid CO2 can effectively extinguish Chinese liquor fires. The larger the diameter of the combustion disk, the more significant the change in mass. The larger the diameter of the combustion disk, the higher the temperature that can be reached by the Chinese liquor pool fire, up to 340 ℃. The extinguishing time under three different combustion disc diameters is 32, 36, and 38s respectively, and there is no re-ignition phenomenon. The highest gas volume fraction of CO2 in the fire scene space can reach 26%. The distribution of CO2 content at measurement points G1-G4 under different combustion disc diameters is as follows: G4 > G3 > G2 > G1. The distribution of CO content is: G3 > G4 > G1 > G2. The distribution of O2 content is G1 > G2 > G3 > G4.

Key words: liquid CO2 fire extinguishing, Chinese liquor pool fire, quality change quantity, temperature, gas concentration

CLC Number: