定向泄爆管道结构对掺氢天然气火焰传播及超压的影响

阳旭峰(), 蒋保平, 杨文, 张坤, 张玉春**()   

  1. 西南交通大学 地球工程与科学学院, 四川 成都 611756
  • 收稿日期:2026-04-05 修回日期:2026-06-20 出版日期:2026-10-20
  • 通信作者:
    ** 张玉春(1980—),男,四川成都人,博士,教授,主要从事隧道及地下空间火灾防治、应急救援技术、智慧消防等方面的研究。E-mail:。
  • 作者简介:

    阳旭峰 (1992—),男,四川泸州人,博士,副教授,主要从事爆炸动力学特征及抑爆减灾技术、锂离子电池燃爆机制及防控策略等方面的研究。E-mail:。

  • 基金资助:
    国家自然科学基金资助(U24A20172); 国家青年科学基金资助(52204241)

Effects of directional venting duct structure on flame propagation and overpressure evolution of hydrogen-blended natural gas

Yang Xufeng(), Jiang Baoping, Yang Wen, Zhang Kun, Zhang Yuchun**()   

  1. Faculty of Geosciences and Engineering, Southwest Jiaotong University, Chengdu Sichuan 611756, China
  • Received:2026-04-05 Revised:2026-06-20 Published:2026-10-20

摘要:

为降低掺氢天然气管道爆炸事故危害,提升输气管道安全水平,通过自主搭建的管道爆炸试验平台,系统对比掺氢天然气,即CH4/H2/空气混合物在无泄爆管道、水平泄爆管道和60°分岔泄爆管道3种条件下的爆炸特性,重点分析不同定向泄爆管道结构对火焰传播特性和预混管道内爆炸超压的影响。研究结果表明:与无泄爆管道的开放空间条件相比,在定向泄爆约束条件下,泄爆管道内发生的剧烈二次爆炸,致使预混管道内爆炸超压与火焰传播速度显著提升;与水平定向泄爆相比,分岔定向泄爆入口处的分岔结构削弱了泄放气体的流速,使火焰锋面传播至泄爆管道的时间延长,推迟了火焰速度和爆炸超压达到峰值的时间;相较于水平定向泄爆管道,分岔定向泄爆管道能够有效降低最大火焰传播速度、最大爆炸超压及最大压力上升速率,降幅分别为9%、30%和24%。

关键词: 定向泄爆, 管道结构, 掺氢天然气, 火焰传播, 爆炸超压, 二次爆炸, 火焰结构

Abstract:

To mitigate explosion hazards in hydrogen-blended natural gas pipelines and enhance the safety level of gas transmission infrastructure, this study independently designed and constructed a pipeline explosion experimental platform. A systematic comparison was conducted on the explosion characteristics of hydrogen-blended natural gas (i.e., CH4/H2/air mixtures) under three configurations: without a venting duct, with a horizontal venting duct, and with a 60° bifurcated venting duct. The study focused on analyzing the influence different directional venting duct structures on flame propagation dynamics and overpressure development inside the pipeline. The results demonstrate that, compared to the open-space condition without a venting duct, the confined directional venting configuration intensifies secondary explosions within the duct, leading to a significant increase in both explosion overpressure and flame propagation speed. In contrast to horizontal directional venting, the bifurcated structure at the entrance of the bifurcated directional venting duct reduces the flow velocity of the vented gas, prolonging the time required for the flame front to propagate into the venting duct and delaying the peak values of both flame speed and explosion overpressure. Compared to the horizontal directional venting duct, the bifurcated design reduces the maximum flame propagation speed, peak explosion overpressure, and maximum rate of pressure rise by 9%, 30%, and 24%, respectively.

Key words: directional venting, duct structure, hydrogen-blended natural gas, flame propagation, overpressure, secondary explosion, flame structure